10 sample questions for the Master Electrician, with the correct answer and an explanation for each. No account needed. Try each one before you open the answer.
Sections covered on the exam: Batteries, Transformers, Generators, Electric Currents, Motors, Meters and Scopes, Measurements, Illumination, Switches, Fuses, National Electrical Code, Insulators and Insulation.
Question 1 · Batteries
Answer: C. 200 Ah
Load current is 1,200 W ÷ 48 V = 25 A, and 25 A × 4 h = 100 Ah must be drawn. Because only half of the rated capacity may be used, the bank must be rated 100 Ah ÷ 0.50 = 200 Ah. 100 Ah ignores the depth-of-discharge limit; 50 Ah multiplies by 0.50 instead of dividing.
Question 2 · Motors
Answer: B. 90 A
Inverse-time breakers are sized at up to 250% of table FLC: 34 × 2.5 = 85 A. 85 A is not a standard size, so 430.52(C)(1) Exception No. 1 permits the next higher standard rating, 90 A. Going two sizes up to 100 A is not permitted without the starting exception.
Question 3 · Switches
Answer: D. 6 ft 7 in
Switches and circuit breakers used as switches must be installed so that the center of the operating handle, at its highest position, is not more than 6 ft 7 in (2.0 m) above the floor or working platform, with exceptions such as busway switches.
Question 4 · Motors
Answer: C. 5,600 W
The feeder or service neutral load for household ranges, ovens and dryers may be calculated at 70% of the demand determined for the ungrounded conductors: 8,000 × 0.70 = 5,600 W.
Question 5 · National Electrical Code
Answer: B. 6 AWG copper
Although Table 250.66 would require 1/0 AWG for 500 kcmil, 250.66(A) states that the part of a GEC that is the sole connection to a rod, pipe or plate electrode need not be larger than 6 AWG copper. A concrete-encased electrode connection need not be larger than 4 AWG copper.
Question 6 · Batteries
Answer: B. 12 batteries: three parallel strings of four in series
Four 12 V batteries in series give 48 V at 100 Ah. Three such strings in parallel give 300 Ah, so 3 × 4 = 12 batteries. Series connections add voltage, and parallel strings add capacity.
Question 7 · Motors
Answer: C. 45 A
Table 430.52 allows nontime-delay fuses at up to 300% of table FLC: 14 × 3 = 42 A. 42 A is not standard, so the next higher standard size, 45 A, is permitted. 25 A is the 175% value for dual-element fuses.
Question 8 · Switches
Answer: A. AC-4
AC-3 covers starting squirrel-cage motors and switching them off while running. AC-4 covers the more severe duty of plugging, reversing and inching, where the contactor breaks locked-rotor current. AC-1 is for resistive loads, and AC-15 for control of electromagnetic loads.
Question 9 · Motors
Answer: D. 63 A
I = P ÷ (1.732 × V × PF). At 0.70: 50,000 ÷ (1.732 × 480 × 0.70) = 86 A. At 0.95: 50,000 ÷ (1.732 × 480 × 0.95) = 63 A. Correcting power factor cuts current, I²R losses and voltage drop.
Question 10 · National Electrical Code
Answer: C. All must be bonded together into one grounding electrode system
All grounding electrodes present at each building must be bonded together to form the grounding electrode system. A metal water pipe must also be supplemented by an additional electrode, because it could later be replaced with plastic.
TTP Prep has 200 Master Electrician practice questions with explanations, timed and mock-exam modes, 516 flashcards, interactive lessons, a printable cheat sheet and a readiness score. Start free, no card needed.